Hỗ trợ trực tuyến

Hỗ trợ kỹ thuât

(+84-4)38771700
  • Sản phẩm bán chạy
  • Panasonic Product

  • Hakko Products

  • SMC Product

  • Schleuniger Products

  • RKC Product

  • adpack products

  • kyowa product

  • t-h-m product

  • Rgl product

  • OTSUKA products

  • OSAWA productS

  • ANEST

  • Other Product


Thông tin: Your browser does not accept cookies. To put products into your cart and purchase them you need to enable cookies.

FB100

Giá: Liên hệ
dsada

The FB100 is a high performance 1/16 DIN size process controller with a more advanced Brilliant II PID, autotuning, advanced tuning, selectable sampling cycle time of 0.05/0.1/0.25 second and 0.1 % of accuracy in short depth housing. 

  • Panel space saving: 74mm depth
  • Numerous inputs and outputs
  • Multi-memory area (Up to 8 sets)
  • Selectable PID control algorithm
  • Easy-setup and Data Monitoring via a standard data port
  • Inter-controller Communication
  • Modbus support

 

Measuring accuracy
Thermocouple Type : K, J, T, E, PLII, U, L
Less than -100°C (-148°F) : ±1.0°C (±1.8°F)
-100 to +500°C (-148 to 932°F) : ±0.5°C (±0.9°F)
More than 500°C (932°F): ±(0.1% of reading + 1 digit)
ƒzƒƒCƒgƒ‰ƒCƒ“
Type : N, S, R, W5Re/W26Re
Less than 0°C (32°F) : ±2.0°C (±3.6°F)
0 to 1000°C (32 to 1832°F) : ±1.0°C (±1.8°F)
More than 1000°C (1832°F): ±(0.1% of reading + 1 digit)
ƒzƒƒCƒgƒ‰ƒCƒ“
Type : B
Less than 400°C (752°F) : ±70.0°C (±126°F)
400 to 1000°C (752 to 1832°F) : ±(1.4°C + 1digit) [±(2.5°F + 1digit)]
More than 1000°C (1832°F): ±(0.1% of reading + 1 digit)
ƒzƒƒCƒgƒ‰ƒCƒ“
Cold junction temperature compensation error ±1.0°C (1.8°F) [Between 5 and 40°C (41 and 104°F)] 
±1.5°C (2.7°F) [Between -10 and 5°C (16 and 41°F), and 40 and 50°C (104 and 122°F)]
ƒzƒƒCƒgƒ‰ƒCƒ“
RTD Less than 200°C (392°F): ±0.2°C (±0.4°F)
More than 200°F(392°F) : ±(0.1% of reading + 1 digit)
ƒzƒƒCƒgƒ‰ƒCƒ“
DC voltage and DC current ±(0.1% of span)

Selectable sampling time among 50ms, 100ms, and 250ms.
Selectable sampling time makes the FB Series suitable for any application ranging from pressure control requiring fast response to precise control requiring highest resolution. The selections are 100ms (factory setting) usually suitable for most of standard applications, 50ms for fast response applications, and 250ms for precise control requiring high-resolution. The PID parameters can be set in 1/10 unit which supports fast and accurate control. Ramp-to-setpoint and output-change-limiter functions are each settable for UP and DOWN so that a special heater can be controlled precisely.
250ms sampling controller 50ms sampling controller
250ms sampling controller explanation drawing 50ms sampling controller explanation drawing


Selectable PID control algorithm
PID control algorithm is selectable in the FB Series to achieve the most precise control for various applications.
PV Derivative PID : suitable for fixed setpoint control (Factory setting)
Deviation Derivative PID : suitable for ramp control using ramp-to-setpoint function and cascade control.
PV derivative type PID control Deviation derivative type PID control
Most adaptive to conventional fixed value control Most adaptive to conventional fixed value control
PV derivative type PID control explanation drawing Deviation derivative type PID control explanation drawing


Advanced Heat/Cool PID algorithm with Undershoot Suppression
Advanced Heat/Cool PID algorithm achieves stable control by the Undershoot Suppression (USS) function, and independent P-I-D settings for both Heat and Cool which are effective for applications with strong cooling gain. Control Response type selection is settable to avoid overshoot at start-up and against external disturbance. The FB Series also offers selection of water cool and air cool PID control algorithm.
Control response parameter USS (Under Shoot Suppression) gain
Control response parameter explanation drawing USS (Under Shoot Suppression) gain explanation drawing
Last Updated: Thứ sáu, 24 Tháng mười một 2017 15:58